作者
Jayaprakash Saththasivam, Kim Choon Ng
发表日期
2008/5/1
期刊
ASHRAE Transactions
卷号
114
期号
1
简介
This paper describes how the performance of chillers can be predicted by the Simple Thermodynamic Model (Gordon-Ng Universal Chiller Model) at steady state conditions that span across assorted coolant temperatures. It focuses on diagnostic capabilities of the simple thermodynamic approach using the published data from a 90-ton centrifugal chiller. Five different types of degrading chiller faults (reduced condenser water flow, condenser fouling, refrigerant overcharge, non-condensable in refrigerant and excessive oil in compressor) were succinctly detected by the model based on physically meaningful parameters of chillers.
引用总数
2009201020112012201320142015201620172018201920202021202220232024133331242541331
学术搜索中的文章